ADW535-1

  • Resettable linear thermal detector
  • Fully electronic pressure sensor
  • 2 configurable relays
  • Accurate and continuous monitoring
  • EN 54-22
  • maximum tube length 115m
  • Description
  • Specifications
  • Contents
  • Downloads

ADW535-1 uses an air-filled sensor tube installed in the area to be monitored; an electronic pressure sensor continuously monitors the tube and compares the variations with the programmed alarm criteria. It incorporates Dynamic Heat Watch (DHW) technology to avoid false alarms due to short temperature increases, and allows setting response classes from A1I to GI according to EN 54-22 and UL/FM and NFPA equivalents 72. Suitable for tunnels, parking lots, cable tunnels, industrial facilities, logistic halls and areas with high temperatures or heavy soiling

  • Securiton
  • Resettable linear thermal detector
  • Fully electronic pressure sensor
  • Incorporates Dynamic Heat Watch (DHW) technology to reduce false alarms
  • Allows precise and continuous monitoring over long distances and critical areas
  • 2 configurable relays
  • IP65 (dust and water resistant housing)
  • EN 54-22
  • maximum tube length 115m
BrandSecuriton
ModelADW535-1 (1 sensor tube)
Power9–30 Vcc (typical 24 Vcc)
Consumption in service≈ 35–43 mA (24 Vcc) according to configuration
Consumption during self-testup to ≈ 210 mA during approx. 180 s
No. of sensor tubes1
Max. length. pipe with EN 54-22to 115 m
Max. length. tube without EN 54-22to 200 m
Response types EN 54-22A1I, A2I, BI, CI, DI, EI, FI, GI
Unit operating temperatureapprox. -30 °C to +70 °C
Inputs / outputs2 relay outputs, open collector outputs, buses for expansion modules (p. e.g. XLM 35)
Event memoryup to ≈ 64 000 events; extended logging with SD card
Housing dimensions 250 × 212 × 134 mm
Degree of protectionIP65
  • Resettable linear thermal detector

alt