TOA-VX-2000DS

  • Emergency power supply EN54 VM-3000
  • Battery charger
  • UPS function
  • Supervised automatic switching
  • 6 DC outputs in case of failure
  • Description
  • Specifications
  • Contents
  • Downloads
  • TOA
  • Emergency power supply system for VM-3000
  • Voice alarm EN54 and general public address system
  • UPS backup in case of power failure
  • Battery charger
  • 6 DC outputs (Max. 25A/salida)
  • Automatic switching
  • Rack 19" 2U
ModelVX‐2000DS
Power supply230 V AC, 50/60 Hz
Energy consumption240 W max.
Applied batteryPanasonic LC-X1265PG/APG (65 Ah)
Charging methodSlow charging
Charging current5 A max.
Load output voltage27,3 V ±0,3 V (to 25 ℃ (77 ゜F))
Temperature correction factor: -40 mV/℃
Power supply input6 Screw terminal M4, distance between barriers: 11 mm (0.43")
DC power supply output6 (25 A max. each) Screw terminal M4, distance between barriers: 11 mm (0,43")
Monitoring connectorFemale connector RJ45 for connecting the Surveillance Frame VX-2000SF.
Straight twisted pair cable (standard TIA/EIA-568A)
Type of monitoring signal: battery check, AC power status, DC power status, charging circuit failure and battery failure
Battery connection1 positive and negative pair of terminals
Applicable cable diameter: AWG 6 - AWG 0 (1/0) (Line resistance inside
of 4 mΩ/total)
2 Cross-sectional area: 16 - 50 mm
Operating temperature0 ℃ to +40 ℃ (32 ゜F to 104 ゜F)
FinishPanel: Sheet steel with surface treatment, black, 30 % brightness, painted
Dimensions482 (width) × 88,4 (height) × 377,6 (depth) mm (18,98" × 3,48" × 14,87")
Weight10,5 kg (23,15 pounds)
AccessoryMounting screw in rack...4, Washer of fibra...4, Blade fuse (40 A)...3,
Fuse (T3.15A L)...1, Power cable (2 m (6,56 pies))...1, sheet aislante...1,Etiqueta of attention (German) …1, Fastening hook …4, Fastening loop …4, Adhesive (Declaration of compliance) …1, Thermal insulation sheet …1
Fuse evaluationBlade fuse (40 A), Blade fuse (7,5 A), Fuse (T3.15A)
Internal resistanceMaximum internal resistance of the battery and its associated circuit, Ri max: 50 mΩ
Current specificationMaximum battery output current consumption: 43,5 A
Maximum continuous output rated current, I max a: 43,5 A
Maximum rated short-time output current, I max b: 43,5 A
Minimum rated output current, I min: 0 A
Cable specificationRecommended cable parameter for DS-SF Link: straight twisted pair cable (standard TIA/EIA-568A)
  • Emergency power supply
  • Installation material
  • User instructions

alt